Red positive, black negative, blue signal/balance. Dot = joined; hop or no dot = not joined. Tags (LINE+, S2-B, +5V, 0V, P−) join every point with the same tag. LINE+ is the pack positive through S2 pole A; 0V in the control box is P− brought up the battery run. 3 V* = source for S1 ON, to be settled.
Control box mounted 20 cm above the battery box roof. Three holes in the control box bottom, one per run, sealed with silicone.
| Run | Cable | Cores |
|---|---|---|
| PV panel → control box | Automotive sheathed 2-core | From the back of the panel, along the bracket, round the corner of the post and up into the control box bottom, with a drip bend. PV+ passes through to the battery run; PV− → 0V |
| Battery box ↔ control box | Automotive sheathed 3-core, about 20 cm | Down from the control box bottom, past the battery box roof by about 5 cm, bend, back up into the battery box. PV+: panel to K1 COM; LINE+: pack P+ through S2 pole A; 0V: pack P−, shared by the panel negative (the SD30CRMA input and battery GND are common) |
| Control box → lantern | Automotive sheathed 2-core | Drip bend at the control box. LAMP (PIR relay NO) and 0V → lamp regulator in lantern base → COB 1 and COB 2 in parallel |
| Box | From | To |
|---|---|---|
| Battery | Pack P+ | S2 pole A COM and pole B COM |
| Battery | S2 pole A outside and inside throws (joined) | F1 (PTC resettable fuse, 30 V 2.5 A) |
| Battery | F1 out = LINE+ | Battery run LINE+; SD30CRMA OUT+ |
| Battery | Battery run PV+ | K1 COM |
| Battery | K1 NC | SD30CRMA IN+ |
| Battery | S2 pole B outside throw (S2-B) | 12 V Mini-360 IN+ |
| Battery | 12 V Mini-360 OUT+ / OUT− | W1209 +12V / GND |
| Battery | W1209 relay pads coil+ / drive | K1 A1+ / A2− |
| Battery | K1 NO | Heater reg (LM2596) IN+ |
| Battery | Heater reg OUT+ / OUT− | Heat sheet red / black |
| Battery | W1209 NTC input (NTC a / NTC b) | Thermistor network: T1+T2 in series and T3+T4 in series, the two branches in parallel (10k). One bead per 8P group centre channel; series joins in packs 2 and 4, parallel joins at top, two leads out |
| Battery | 12 V Mini-360 IN−, heater reg IN−, SD30CRMA IN− and OUT− | P− |
| Battery | Pack P− | Battery run P− |
| Battery | BMS B−, B1, B2, B3, B+ | Pack −, G1/G2, G2/G3, G3/G4, pack + |
| Control | PV run + | Battery run PV+ (joined through) |
| Control | PV run − | 0V |
| Control | Battery run LINE+ | Daylight relay COM; PIR 5 V reg IN+; daylight Mini-360 IN+ |
| Control | Battery run P− | 0V |
| Control | Both 5 V regulators IN− and − | 0V |
| Control | Daylight Mini-360 OUT+ / OUT− | Daylight sensor VCC / GND |
| Control | Daylight sensor DO (AO not used) | Daylight relay COIL+ |
| Control | Daylight relay COIL− | 0V |
| Control | Daylight relay NIGHT (DAY not used) | PIR relay COM |
| Control | PIR relay NO | Lantern run LAMP |
| Control | 0V | Lantern run 0V |
| Control | PIR 5 V reg + | PIR sensor VCC |
| Control | PIR sensor OUT | Mode switch S1 AUTO |
| Control | 3 V* (to be settled) | Mode switch S1 ON |
| Control | Mode switch S1 COM (SPDT on/on, waterproof, bottom face with rubber boot) | PIR relay COIL+ |
| Control | PIR relay COIL−, PIR sensor GND | 0V |
| Lantern | Lantern run LAMP / 0V | Lamp reg IN+ / IN− (lantern base) |
| Lantern | Lamp reg OUT+ / OUT− | COB 1 and COB 2 in parallel |
Daylight sensor: the photodiode is lifted off the LM393 board onto two short leads and set at an angle in an oversize hole in the control box top, facing SSE, so it trips as dusk settles in rather than when the sky overhead goes dark.
Battery box: pack, BMS, SD30CRMA, W1209 with its 12 V Mini-360, K1, the heater regulator and S2. Three leads to the control box: PV+ in, LINE+ out, and a shared 0V. As a standalone pack it charges through the MPPT input, so it needs a source of about 18 V or more.
S2 outside: LINE+ live (charging and load), W1209 live. Off: everything off, including charging. Inside: LINE+ live, W1209 unpowered, so K1 rests on NC and charging is normal. S2 is DPDT on/off/on: pole A carries LINE+ in both on positions, pole B feeds the W1209 in outside only. The MPPT output joins LINE+ after S2 and F1, so off stops charging as well as the load.
F1 is a resettable PTC fuse (30 V 2.5 A) on LINE+, protecting the run and every relay contact downstream. It resets by itself once the fault is cleared and it cools.
K1 is the W1209 relay, a Fujitsu VB-12STBU-5 (12 V coil, 5 A contacts), mounted off the board in the battery box. NC: panel to the MPPT, charging. NO: panel to the heater regulator and heat sheet, no charging. The pack is never charged while the W1209 is calling for heat, and the heater only ever runs from the panel.
The daylight relay only switches the pack to the PIR relay and lantern at night; its DAY contact is not used.
Changing to a SELV rail: remove the battery box and the panel with its run; connect LINE+ and 0V to the rail; insulate and leave the PV+ core unconnected (or remove it). Run the rail at a regulated 20 V DC: 3 V under the Mini-360's 23 V input limit, with about 8 V of drop available before the lamp LM2596 falls below the roughly 12 V it needs for 10.5 V out. Runs of up to 150 m each way from the supply. The supply must hold its setting at no load and not overshoot at start-up.
Mode switch S1 switches the PIR relay coil signal, not power: AUTO = PIR controls the lamp at night; ON = lamp on all night. The daylight relay still decides day and night in both positions.